Lockout/tagout isolates a machine's energy sources before anyone works on it, so it can't start up or release stored energy while someone's hands are inside it — and only the person who locked it can unlock it.
CCOHS ties the term to the national standard directly: “lockout is defined in the Canadian standard CSA Z460-20 as the placement of a lockout device on an energy-isolating device in accordance with an established procedure.” On site that means physically isolating every relevant energy source before maintenance, repair or clearing a jam — electrical, hydraulic, pneumatic, mechanical, gravitational and chemical are each named as sources that need their own isolation and residual-energy dissipation step, not just the obvious electrical shutoff.
Two rules do the heavy lifting once a lock is applied. Removal is restricted to the person who placed it — “ONLY the authorized individual who placed the lock and tag onto the system is the one who is permitted to remove them” — and where more than one worker is exposed, each applies their own: “there should be as many locks on the system as there are people working on it.” A supervisor removing someone else’s lock because that worker has already left for the day is exactly the failure mode the rule exists to prevent.
An HVAC sub is servicing a rooftop unit wired into the building's electrical panel. Before opening the unit, the two technicians on the job notify the building operator, shut down and isolate the circuit at the panel, bleed any residual stored energy in the unit's capacitors, and each applies their own lock to the panel — two locks, because two people are exposed to the same energy source. Neither can remove the other's lock. Each removes only their own once their own work is verified complete and safe, and the unit stays de-energized until every lock assigned to that job is off.
See also: Confined space entry permits · The FLHA form · AI site safety monitoring cameras.